Research processes of oil and paper insulation of high-voltage equipment during operation Research Processes of Oil and Paper Insulation of High- Voltage Equipment during Operation
Author
G. Sree Lakshmi
Rubanenko, O.
Rubanenko, O.
Hunko, I.
Рубаненко, О. Є.
Рубаненко, О. О.
Гунько, І. О.
Date
2020Metadata
Show full item recordCollections
- Наукові роботи каф. ЕСС [342]
Abstract
The article analyzes the factors that accelerate the aging process of the oil-paper insulation of the condenser
type and shorten its service life. Attention is drawn to the fact that the breakdown of flat insulation made of condenser
paper occurs at the location of the inclusion, which approximately corresponds to the field of uniform field. An example
of damage to the insulation of a current transformer due to its aging and moisture is given. This work was analysed the
influence of thickness and density of paper, grade of mineral oil on short-term electrical strength. The characteristics of
the insulating papers of the permeable composition largely determine the electrical strength of the paper-oil
insulation.Since paper-oil insulation consists of a series of successive layers of paper and oil, it is advisable to present
such insulation by the equivalent scheme shown in fig. 1, in which the thickness of the paper-oil dielectric is divided into
two layers: paper (fiber) and mineral oil, connected in series.