Визначення причин виникнення та характеристик однофазних замикань на землю розподільчих мережах напругою 6-35 кВ
Author
Кутін, В. М.
Кутіна, М. В.
Ковальов, А. І.
Романюк, М. І.
Date
2023Metadata
Show full item recordCollections
Abstract
The analysis of statistical data showed that the most common type of damage to distribution networks is single-phase
earth faults, which account for 80% of all types of damage. The main cause of earth faults is the formation of shunt connections between the
current-conducting part and the earth. The reason for their occurrence is external factors: lightning overlapping insulation, overlapping
insulation with tree branches, ice, wind load, vibration of networks, burning of wooden supports, damage to supports by various mechanisms.
Cable networks are damaged due to a violation of their mechanical stability and due to the aging of the insulation between the phases and
the belt insulation. In the work, the classification of single-phase earth faults is performed. In general, the whole variety of single-phase earth
faults can be divided into two groups - non-arcing and arcing. An accurate mathematical description of the processes of single-phase earth
faults accompanied by an electric arc is a significant difficulty due to the fact that the electrical resistance of a steadily burning arc is a nonlinear function of the current flowing through it. A. M. Lyapunov's stability theory was used to find out the conditions of arc stability during a
single-phase earth fault. The grid replacement scheme for single-phase arcing to the ground is constructed. It was determined that the arc is
formed under the action of two currents: from the discharge of the capacity of the small circuit (free current) and from the EMF source of the
large circuit (forced current). Since the nature of the transition process is mainly determined by the free component, its analysis was carried
out. It was determined that it is extremely important for practical purposes to acquire quantitative values not only of resistance, but also of
the duration of existence of self-eliminating circuits.
The parameters of the single-phase ground fault circuit in the electrical network, motors, transformers, the stability conditions of
single-phase ground faults have been investigated Аналіз статистичних даних показав, що основними причинами виникнення однофазних
замикань на землю (ОЗЗ) в мережах з повітряними лініями електропередачі є зовнішні збурюючі дії: перекриття
ізоляції, розрив ізоляторів, оплавлення механічних елементів, обриву провідників, падіння опор, ожеледиця,
допущення обслуговуючим персоналом технологічних порушень. Кабельні мережі пошкоджуються через
порушення їх механічної стійкості і внаслідок старіння між фаз та поясної ізоляції. В роботі виконано
класифікацію ОЗЗ. Досліджені параметри ланцюга ОЗЗ в електричній мережі, двигунах, трансформаторах, умови
стійкості ОЗЗ
URI:
http://ir.lib.vntu.edu.ua//handle/123456789/38106