Метод контролю технічного стану ізоляції електрообладнання блоку «генератор-трансформатор»
Вантажиться...
Файли
Дата
Автори
Назва журналу
Номер ISSN
Назва тому
Анотація
Significant wear of the main electrical equipment of the power supply scheme (synchronous generators, complete shielded power
lines, transformers) of thermal and nuclear power plants, implementation of the policy of extending the service life of existing power units,
and gradual implementation of equipment repair strategies according to technical condition determines the relevance of development of
new and improvement of existing systems for monitoring the technical condition of electrical equipment in general and its insulation
characteristics in particular. Insulation diagnostics, relay protection devices and information-measuring systems currently operated on
power units do not allow tracking changes in electrical insulation parameters of electrical equipment such as insulation resistance and
capacitance relative to ground and tangent angle of dielectric loss detection that makes detection of defects in isolation at an early stage of
their development impossible. Relay protection devices can be insensitive to single-phase earth faults of the stator winding near the neutral
and with a symmetrical decrease in the insulation parameters of the stator winding, as well as malfunction when starting units due to
voltage asymmetry in generator phases.
The method of control of technical condition of electrical equipment insulation in the generator-transformer unit circuit is
proposed, which is based on combined superimposition of direct current and alternating current with frequency less than industrial, control
of discharge of precharged capacitor and control of alternating current flow with Rogovsky coils. The proposed method will detect both
abrupt and gradual changes in the technical condition of the insulation of electrical equipment of the "generator-transformer" unit, improve
the quality of planning of repair work and speed up the search for faulty elements in case of damage.
Опис
Ключові слова
УДК
Тип документа
Мова
ISSN
Бібліографічний опис
Кутін В. М. Метод контролю технічного стану ізоляції електрообладнання блоку «генератор-трансформатор» [Текст] / В. М. Кутін, М. В. Кутіна, О. О. Шпачук // Вісник Хмельницького національного університету. Серія «Технічні науки». – 2022. – № 3 – С. 138-142.