Cтатистичні дослідження закономірностей зміни опору ізоляції мереж оперативного постійного струму гідроелектростанцій
Вантажиться...
Дата
Назва журналу
Номер ISSN
Назва тому
DOI
Анотація
The possibility of establishing patterns of change in the insulation resistance of the operative dc hydroelectric power. Established
that the most common type of violations in these networks is the closure of one pole to the ground. The existing methods and of general
network control isolation, and certainly restrict their use. Definitely analytical dependence probability decreases the insulation resistance of
the operative dc Hydropower of controlled parameters and based dependency probability correct prediction of drag reduction Pole to 20
ohms depending on the size of the previous shortterm reduction of resistance. A use established depending Stay predicting reductions in
insulation resistance to actuation setpoint control device isolation , enabling operational staff to power plants, electric power systems and
electrical grids businesses to take action on elimination of places with potentially unreliable insulation will increase the reliability of relay
protection and automation . The method of selecting the optimal values of diagnostic parameters for devices of general network control
isolation of the operative DC.
Опис
Ключові слова
УДК
Тип документа
Мова
Є частиною
ISSN
Бібліографічний опис
Рубаненко О. Є. Статистичні дослідження закономірностей зміни опору ізоляції мереж оперативного постійного струму гідроелектростанцій [Текст] / О. Є. Рубаненко, І. А. Жук, О. О. Рубаненко // Вісник Хмельницького національного університету. Серія "Технічні науки". - 2014. - № 3. - С. 110-113.