dc.contributor.authorКучанський, В. В.uk
dc.contributor.authorЗайцев, Є. О.uk
dc.contributor.authorКоваленко, О. М.uk
dc.contributor.authorKuchanskyy, V. V.en
dc.contributor.authorZaitsev, Ye. O.en
dc.contributor.authorKovalenko, O. M.en
dc.date.accessioned2025-10-13T07:50:23Z
dc.date.available2025-10-13T07:50:23Z
dc.date.issued2025
dc.identifier.citationКучанський В. В., Зайцев Є. О., Коваленко О. М. Аналіз коливань проводів повітряних ліній електропередавання під час плавлення ожеледі постійним струмом // Вісник Вінницького політехнічного інституту. 2025. № 2. С. 81-90.uk
dc.identifier.issn1997-9274
dc.identifier.urihttps://ir.lib.vntu.edu.ua//handle/123456789/49782
dc.description.abstractThe article analyzes the relationship between the ice melting current, temperature distribution and vibration of overhead power line wires, which is based on the use of the series connection method to obtain the connection equation between the electrical and thermal energy released during the process of melting ice on wires with a direct current. Usually, in the case of calculating ice melting modes, the problem of choosing such a melting current value is solved, at which, under given meteorological conditions, ice will be removed in a given time. For a specific ice melting scheme, such a current remains practically unchanged for all weather conditions, therefore, there is always a fear that the current value in this scheme may be insufficient for successful ice melting under certain unfavorable, but possible ice wall thickness, wind speed and ambient temperature. The article, based on the refined model of ice melting, considers the method of determining the actual range of meteorological conditions under which, for a given current value, successful ice melting is ensured. Usually, in the case of calculating ice melting modes, the problem of choosing such a melting current value is solved, at which, under given meteorological conditions, the ice will melt in a given time. Such a formulation of the problem is suitable for overhead lines equipped with special ice melting installations with an adjustable current value. provided that the ice melting current in all weather conditions does not exceed the permissible value. For overhead lines that do not have such installations, the ice melting current is not regulated, its value must be chosen taking into account a number of restrictions (mechanical strength of wires, power supply capacity, ice melting power scheme, length of the ice melting zone, etc.). Experience in operating electric networks shows that ice-wind accidents on overhead lines are among the most severe, and can disrupt the power supply of large economic areas of the regions of Ukraine. The issue of preventing ice-wind accidents on overhead lines is also relevant for main electric networks. It should be noted the significant economic damage from ice-wind accidents on the Western electric power system in the autumn-winter periods: 2004—2005, 2010—2011 and 2012—2013.en
dc.description.abstractПроаналізовано взаємозв’язок між струмом плавлення ожеледі, розподілом температури та вібрацією проводів повітряної лінії електропередавання, який ґрунтується на використанні методу послідовного зв’язку для отримання рівняння зв’язку між електричною та тепловою енергіями, що виділяється під час танення ожеледі на проводах постійним струмом. Зазвичай у випадку розрахунку режимів плавки ожеледі вирішується завдання вибору такого значення струму плавки, за якого в заданих метеорологічних умовах ожеледь буде видалена за заданий час. Для конкретної схеми плавки ожеледі такий струм залишається практично незмінним для всіх погодних умов, тому завжди є побоювання, що значення струму в цій схемі може виявитися недостатнім для успішної плавки ожеледі за умов певної несприятливої, але можливої товщини стінки ожеледі, швидкості вітру і температури навколишнього середовища. У статті на основі уточненої моделі плавки ожеледі розглянуто методику визначення дійсної області метеорологічних умов, за яких у разі заданого значення струму забезпечується успішна плавка ожеледі. Зазвичай у випадку розрахунку режимів плавки ожеледі вирішується завдання вибору такого значення струму плавки, за якому в заданих метеорологічних умовах ожеледиця буде розплавлена за заданий час. Така постановка задачі придатна для повітряних ліній, обладнаних спеціальними установками плавки ожеледі з регульованим значенням струму. за умови, що струм плавки ожеледі у всіх погодних умовах не перевищує допустимого значення. Для повітряних ліній, що не мають таких установок струм плавки ожеледі не регулюється, його значення доводиться вибирати з урахуванням низки обмежень (механічної міцності дротів, потужності джерел живлення, схеми живлення для плавлення ожеледі, довжини зони плавлення ожеледі тощо). Досвід експлуатації електричних мереж показує, що ожеледь-вітрові аварії на ПЛ належать до найтяжчих, можуть дезорганізувати електропостачання великих економічних районів регіонів України. Питання запобігання ожеледь-вітровим аваріям на ПЛ актуальне і для магістральних електричних мереж. Варто зазначити суттєву економічну шкоду від ожеледь-вітрових аварій на Західній електроенергетичній системі в осінньо-зимові періоди: 2004—2005, 2010—2011 та 2012—2013.uk
dc.language.isouk_UAuk_UA
dc.publisherВНТУuk
dc.relation.ispartofВісник Вінницького політехнічного інституту. № 2 : 81-90.uk
dc.relation.urihttps://visnyk.vntu.edu.ua/index.php/visnyk/article/view/3219
dc.subjectожеледоутворенняuk
dc.subjectповітряна лінія електропередаванняuk
dc.subjectплавлення льоду постійним струмомuk
dc.subjectвібраційні характеристикиuk
dc.subjectice formationen
dc.subjectoverhead power lineen
dc.subjectice melting by direct currenten
dc.subjectvibration characteristicsen
dc.titleАналіз коливань проводів повітряних ліній електропередавання під час плавлення ожеледі постійним струмомuk
dc.title.alternativeAnalysis of Vibrations of Overhead Power Lines During Ice Melting with Direct Currenten
dc.typeArticle, professional native edition
dc.typeArticle
dc.identifier.udc681.316.1
dc.relation.referencesZou Chenqiao, Peng Ping, Liu Yonggang, and Xu Hao, “Analysis of the Influence of Remanence on the Performance of Current Transformer Caused by DC Ice Melting of Transmission Lines,” Journal of Physics: Conference Series, no. 2503 (1), 2023.en
dc.relation.referencesWen Zuopeng, Lou Wenjuan, and Jiang Xiong, “Galloping stability of a 3-DOF conductor model considering inertial coupling and anti-galloping mechanism of inertial mass,” Journal of Vibration Engineering, no. 35 (4), pp. 1029-1036, 2022.en
dc.relation.referencesS. S Shovkoplyas, A. I. Kryukov, A. Y. Kutuzov, and E. I. Satsuk, “Operation of Current Protection for the Zero Sequence of Overhead Electric Power Transmission Lines Taking the Circuit for Ice Melting on its Lightning-Protection Cables into Account,” Power Technology and Engineering, no. 56 (2), 2023.en
dc.relation.referencesWen Zuopeng, and Liang Hong-chao, “Optimization for galloping wind speed control of ultra-high-voltage iced conductors with large span using TTMD,” Journal of Vibration Engineering, no. 34 (5), pp. 934-942, 2021.en
dc.relation.references«Енергетики зафіксували рекордну ожеледь на дротах ЛЕП,» UA.NEWS, 15 Січня 2024, [Електронний ресурс]. Режим доступу: https://ua.news/ua/ukraine/energetiki-zafiksuvali-rekordnu-ozheled-na-drotah-lep .uk
dc.relation.referencesLouis M. Schellenberg, Thomas J. Newton, and Gary R., “Hunt On the rotation of melting ice disks, “ Journal Environmental Fluid Mechanics, no. 23 (2), 2023.en
dc.relation.referencesZhu He, et al., “Dynamic response analysis of sub-conductor non-synchronous deicing during DC ice-melting of fourbundle conductor spacer system,” Journal of Vibration and Shock, no. 42 (1), pp. 282-291, 2023.en
dc.relation.referencesZhu He, et al., “DC ice-melting operation of the ground wire based on the characteristic investigation of the thermal structure coupling effect,” Electric Power Systems Research, 218, 2023.en
dc.relation.referencesZhu Gaojia, et al., “Finite formula temperature field calculation technology and its application in the analysis of permanent magnet motor,” [J] Proceedings of the CSEE, no. 37 (S1), pp. 152-161, 2017.en
dc.relation.referencesYang Lei, et al., “Thermotactic habit of gas hydrate growth enables a fast transformation of melting ice,” Applied Energy, 331, 2023.en
dc.relation.referencesWen Yi, et al., “Research on Risk Assessment and Suppression Measures for Ice-Shedding on 500 kV Compact Overhead Lines,” Energies, no. 15 (21), 2022.uk
dc.relation.referencesLou Wenjuan, et al., “Jump height of an iced transmission conductor considering joint action of ice-shedding and wind,” Cold Regions Science and Technology, 199, 2022.en
dc.relation.referencesLou Wenjuan, Zhang Yuelong, and Huang Mingfeng, “Study on amplification factor of jump height of crescent-shaped iced transmission conductor following ice shedding under wind action,” Journal of Vibration and Shock, no. 41 (21), pp. 272-278, 2022.en
dc.relation.referencesZhuang Wenbing, et al., “Estimation model of transmission line icing dynamic process based on micrometeorological monitoring,” Power System Protection and Control, no. 47 (14), pp. 87-94, 2019.en
dc.relation.referencesMeng Zhigao, “Study on DC ice melting process and model of optical fiber composite overhead ground line (OPGW),” Chongqing University, 2017.en
dc.relation.referencesLu J, et al., “An Analysis of the Reliability of a New Dataset of Transmission Line Icing Thickness in Southern China,” Journal of Applied Meteorology and Climatology, no. 58 (2), 2019.en
dc.relation.referencesJiazheng Lu, et al., “Low-Harmonic DC Ice-Melting Device Capable of Simultaneous Reactive Power Compensation,” Energies, no. 11, pp. 2-17, 2018.en
dc.relation.referencesTang Rui, “Establishment of the dynamic model of de-icing of trans-mission line and its application in induced deicing,” Jiangsu: Nanjing University of Science and Technology, 2017.en
dc.relation.referencesZhu He, Wang Gang, and Guo Xin, “Influences of ice crystal on aerodynamic characteristics of a 3D iced conductor,” Journal of Vibration and Shock, no. 40 (1), pp. 212-217, 2021.en
dc.relation.referencesЄ. Зайцев, В. Кучанський, і І. Гунько, Підвищення експлуатаційної надійності та ефективності роботи електричних мереж та електроустаковання, моногр. Publishing House «European Scientific Platform», 2021, 156 р., [Електронний ресурс]. Режим доступу: https://doi.org/10.36074/penereme-monograph.2021 .uk
dc.relation.referencesO. Zaitsev and V. V. Kuchanskyy, “Corona discharge problem in extra high voltage transmission line,” in Systems Decision and Control in Energy II, Springer, pp. 3-30, 2021.en
dc.relation.referencesV. Kuchanskyy, and I. O. Zaitsev, “Corona Discharge Power Losses Measurement Systems in Extra High Voltage Transmissions Lines,” in 2020 IEEE 7th International Conference on Energy Smart Systems (ESS), 2020, pp. 48-53. https://doi.org/10.1109/ESS50319.2020.9160088 .en
dc.relation.referencesI. Zaitsev, A. Levytskyi, and V. Bereznychenko “Hybrid diagnostics systems for power generators faults: systems design principle and shaft run-out sensors,” in “Power systems research and operation: Selected problems,” Kyrylenko O., Zharkin A. and other, Eds., Springer, 2021, pp. 71-98. https://doi.org/10.1007/978-3-030-82926-1_4 .en
dc.relation.referencesЄ. Зайцев, В. Березниченко, С. Закусило, і А. Антоненко, «SMART засоби визначення аварійних станів в розподільних електричних мережах міст,» Таврійський науковий вісник, серія: Технічні науки, № 5, с. 3-12, 2022. https://doi.org/10.32851/tnv-tech.2022.5.1 .uk
dc.relation.referencesС. А. Закусило, і Є. О. Зайцев, «Використання технології LoRaWAN в системах інформаційного обміну засобів контролю та діагностування енергетичного обладнання,» Сучасні методи, інформаційне, програмне та технічне забезпечення систем керування організаційно-технічними та технологічними комплексами, матер. X Міжнародної науковотехнічної Internet-конференції, 24 листопада 2023., Київ, Україна: НУХТ, 2023, с. 183. [Електронний ресурс]. Режим доступу: https://nuft.edu.ua/naukova-diyalnist/naukovi-konferencii .uk
dc.identifier.doihttps://doi.org/10.31649/1997-9266-2025-179-2-81-90