Показати скорочену інформацію

dc.contributor.authorTrach, I. V.en
dc.contributor.authorBělík, М.en
dc.contributor.authorRubanenko, O.en
dc.contributor.authorMiroshnyk, V.en
dc.contributor.authorBlinov, I.en
dc.contributor.authorРубаненко, О. О.en
dc.date.accessioned2026-09-22T13:37:32Z
dc.date.available2026-09-22T13:37:32Z
dc.date.issued2026en
dc.identifier.citationTrach I., Bělík M., Rubanenko O., Miroshnyk V., Blinov I. Simulation of voltage control processes in low-voltage microgrid nodes with renewable energy sources and energy storage system // Electrical Engineering & Electromechanics. 2026. no. 4. P. 84-91. DOI: https://doi.org/10.20998/2074-272X.2026.4.11.en
dc.identifier.issn2074-272Xen
dc.identifier.urihttps://ir.lib.vntu.edu.ua/handle/123456789/54646
dc.description.abstractРозвиток мікромереж низької напруги (ММ НН) з відновлювальними джерелами енергії потребує забезпечення ефективного регулювання параметрів їх режимів, зокрема напруги. Проблема регулювання напруги в ММ НН підсилюється використанням на практиці систем віддаленого управління інверторами, що формують мережу (GFI), в умовах обмеженої швидкості передавання даних. Мета. Визначення особливостей локального регулювання напруги у вузлах ММ НН, приєднаних до систем розподілу, з використанням реактивної потужності GFI, зокрема оцінювання залежності коефіцієнта droop-control від параметрів мережі та визначення часових інтервалів квазі-стаціонарності. Методологія. Дослідження виконано з використанням нової розробленої розрахункової моделі у середовищі PowerDynamics.jl для аналізу динаміки ММ НН, яка має переважно активний характер опору фідерів та враховує специфіку роботи GFI. Результати. Встановлено, що режими ММ НН, приєднаних до системи розподілу, на інтервалах понад 60 с можна вважати квазі-стаціонарними, що дозволяє застосовувати статичні характеристики регулювання без урахування швидких перехідних процесів. Проаналізовано роботу моделі в режимах зниження реактивної потужності на вході мікромережі за допомогою PI-контролера та підтримки заданого значення реактивної потужності GFI. Наукова новизна. Розроблено нову розрахункову модель, використання якої, на відміну від існуючих, дозволяє виконати порівняння різних методів розподілу реактивної потужності між групою розосереджених джерел енергії та дослідити особливості локального регулювання напруги з використанням GFI. Практична значимість. З використанням розробленої моделі виконано аналіз та визначено залежності коефіцієнта droop-control по напрузі від значення реактивної потужності GFI та встановлені інтервали квазі-стаціонарності для потужності та напруги в ММ НН. З використанням розробленої моделі підтверджена ефективність локального регулювання напруги з використанням реактивної потужності GFI в різних режимах роботи мікромережі. Сформовано практичні рекомендації до налаштування параметрів GFI та швидкості передачі інформації в системах управління ММ НН. Бібл. 56, табл. 2, рис. 7.en_US
dc.description.abstractIntroduction. The development of low-voltage microgrids (LV MG) with renewable energy sources requires effective control of their operating parameters, in particular voltage. The problem of voltage control in MG is exacerbated by the practical use of remote control systems for grid-forming inverters (GFIs) under conditions of limited data transmission speed. Goal. Identification of the features of local voltage control in LV MG nodes connected to distribution systems using reactive power of GFIs, in particular to assess the dependence of the droop-control coefficient on network parameters and to determine quasi-stationary time intervals. Methodology. The study was carried out using a newly developed imitation model in the PowerDynamics.jl environment for analyzing the dynamics of LV MGs, which are characterized by predominantly active feeder resistance and take into account the specific operating features of GFIs. Results. It has been established that the operating modes of LV MG connected to the distribution system can be considered quasi-stationary over intervals longer than 60 s, which allows the use of static control characteristics without taking into account fast transient processes. The operation of the model was analyzed under conditions of reactive power reduction at the MG input using a PI controller and maintaining a specified value of GFI reactive power. Scientific novelty. A new computational model has been developed which, unlike existing ones, enables comparison of different methods of reactive power distributing among a group of distributed energy sources and investigation of the features of voltage regulation using GFIs. Practical value. Using the developed model, an analysis was performed and the dependence of the voltage droop-control coefficient on the GFI reactive power was determined. Quasi-stationary intervals for power and voltage in LV MGs were established. The developed model confirms the effectiveness of voltage control through GFI reactive power in different MG operating modes. Practical recommendations for setting GFI parameters and information transfer speed in LV MG control systems were formed. References 56, tables 2, figures 7.uk_UA
dc.language.isoen_USen_US
dc.publisherNational Technical University «Kharkiv Polytechnic Institute»,en
dc.relation.ispartofElectrical Engineering & Electromechanics. no. 4 : 84-91.en
dc.subjectmicrogriden
dc.subjectquasi-stationary state intervalsen
dc.subjectgrid-forming inverteren
dc.subjectPV-generationen
dc.subjectreactive poweren
dc.subjectмікромережаen
dc.subjectінтервали квазістаціонарностіen
dc.subjectмережеутворюючий інверторen
dc.subjectсонячна генераціяen
dc.subjectреактивна потужністьen
dc.titleSimulation of voltage control processes in low-voltage microgrid nodes with renewable energy sources and energy storage systemen
dc.typeArticle, professional native edition
dc.identifier.udc621.311en
dc.relation.referenceshttps://eie.khpi.edu.ua/article/view/366081en
dc.identifier.doihttps://doi.org/10.20998/2074-272x.2026.4.11en
dc.identifier.orcidhttps://orcid.org/0000-0002-3345-2324en
dc.identifier.orcidhttps://orcid.org/0000-0002-9907-5365en
dc.identifier.orcidhttps://orcid.org/0000-0002-2660-182Xen
dc.identifier.orcidhttps://orcid.org/0000-0001-9036-7268en
dc.identifier.orcidhttps://orcid.org/0000-0001-8010-5301en


Файли в цьому документі