dc.identifier.citation | Belik M., Kuchanskyy V., Rubanenko O. Method for Determining the Resonant Frequencies of Extra High Voltage Power Transmission Line. Przeglad Elektrotechniczny. 2023. № 10. Pp. 39-42. DOI: 10.15199/48.2023.10.7. | uk |
dc.identifier.issn | 0033-2097 | |
dc.identifier.uri | http://ir.lib.vntu.edu.ua//handle/123456789/39052 | |
dc.description.abstract | W pracy zaproponowano model matematyczny wyznaczania częstotliwości rezonansowej linii 750 kV względem nieobciążonego
transformatora oraz zbadano możliwość wystąpienia przepięć w liniach 750 kV na 2. harmonicznej. Opracowano obwód rezonansowy do
wyznaczania częstotliwości drgań własnych linii elektroenergetycznej ultrawysokiego napięcia w celu analizy warunków przepięć przy składowych
wyższych harmonicznych. Otrzymuje się wyrażenia analityczne w celu określenia stopnia wpływu wartości parametrów linii na częstotliwość
rezonansową linii. W artykule przedstawiono zależność między trybem pracy linii najwyższych napięć a autotransformatorem (transformatorem) na
warunki występowania przepięć. Podano wyrażenia analityczne do oceny wpływu stopnia kompensacji mocy ładowania na wartości parametrów
modowych elektroenergetycznej linii przesyłowej najwyższych napięć | pl |
dc.description.abstract | The paper proposes a mathematical model for determining the resonant frequency of a 750 kV line relative to an unloaded transformer and studies the possibility of overvoltages in 750 kV lines at the 2nd harmonic. A resonant circuit has been compiled to determine the natural frequencies of an ultrahigh voltage power line to analyze the conditions for overvoltages at higher harmonic components. Analytical expressions are obtained to determine the degree of influence of the line parameters` value on the line`s resonant frequency. The paper presents the relationship between the operating mode of an ultra-high voltage power line and an autotransformer (transformer) on the conditions for the existence of overvoltages. Analytical expressions for evaluating the influence of the degree of charging power compensation on the values of the mode parameters of the ultra-high voltage power transmission line are given. | en |
dc.language.iso | en | en |
dc.publisher | Stowarzyszenie Polskich Inżynierów Elektryków i Elektroników | pl |
dc.relation.ispartof | Przeglad Elektrotechniczny. № 10 : 39-42. | pl |
dc.subject | resonance overvoltages | en |
dc.subject | nonsinusoidal mode | en |
dc.subject | no-load autotransformer | en |
dc.subject | resonant frequenc | en |
dc.subject | przepięcia rezonansowe | pl |
dc.subject | tryb niesinusoidalny | pl |
dc.subject | autotransformator bez obciążenia | pl |
dc.subject | częstotliwość rezonansowa | pl |